| Voltage |
| Range |
1000 V |
| Maximum Resolution |
0.1 V |
| Intrinsic Accuracy at Reference Conditions (% of Reading + % of Full Scale) |
±(0.2% + 0.01%) |
| Frequency |
| Range |
42.5 to 69 Hz |
| Maximum Resolution |
0.01 Hz |
| Intrinsic Accuracy at Reference Conditions (% of Reading + % of Full Scale) |
±(0.1%) |
| Aux Input |
| Range |
±10 V DC |
| Maximum Resolution |
0.1 mV |
| Intrinsic Accuracy at Reference Conditions (% of Reading + % of Full Scale) |
±(0.2% + 0.02%) |
| Voltage Min/Max |
| Range |
1000 V |
| Maximum Resolution |
0.1 V |
| Intrinsic Accuracy at Reference Conditions (% of Reading + % of Full Scale) |
±(1% + 0.1%) |
| Current Min/Max |
| Range |
Defined by accessory |
| Maximum Resolution |
Defined by accessory |
| Intrinsic Accuracy at Reference Conditions (% of Reading + % of Full Scale) |
±(5% + 0.2%) |
| THD on Voltage |
| Range |
1000% |
| Maximum Resolution |
0.1% |
| Intrinsic Accuracy at Reference Conditions (% of Reading + % of Full Scale) |
±0.5 |
| THD on Current |
| Range |
1000% |
| Maximum Resolution |
0.1% |
| Intrinsic Accuracy at Reference Conditions (% of Reading + % of Full Scale) |
±0.5 |
Active Power P Active Energy Ea |
| Influence Quantity |
PF ≥0.99 |
Apparent Power S Active Energy Eap |
| Influence Quantity |
0 ≤PF ≤1 |
Reactive Power Q Reactive Energy Er |
| Influence Quantity |
0 ≤PF ≤1 |
| Additional Uncertainty in % of Range |
| Influence Quantity |
VP-N <250 V |
| Power Supply |
| Voltage Range |
100 to 500 V using safety plug input when powering from the measurement circuit 100 to 240 V using standard power cord (IEC 60320 C7) |
| Power Consumption |
Maximum 50 VA (max. 15 VA when powered using IEC 60320 input) |
| Efficiency |
>68.2% (in accordance with energy efficiency regulations) |
| Maximum No-Load Consumption |
<0.3 W only when powered using IEC 60320 input |
| Mains Power Frequency |
50/60 Hz ± 15% |
| Battery |
Li-ion 3.7 V, 9.25 Wh, customer-replaceable |
| On-Battery Runtime |
Four hours in standard operating mode, up to 5.5 hours in power saving mode |
| Charging Time |
<6 hours |
| Data Acquisition |
| Resolution |
16-bit synchronous sampling |
| Sampling Frequency |
10.24 kHz at 50/60 Hz, synchronized to mains frequency |
| Input Signal Frequency |
50/60 Hz (42.5 to 69 Hz) |
| Circuit Types |
1-ϕ, 1-ϕ IT, split phase, 3-ϕ delta, 3-ϕ wye, 3-ϕ wye IT, 3-ϕ wye balanced, 3-ϕ Aron/Blondel (2-element delta), 3-ϕ delta open leg, currents only (load studies) |
| Data Storage |
Internal flash memory (not user replaceable) |
| Memory Size |
Typical 10 logging sessions of 8 weeks with 1-minute intervals and 500 events |
| Basic Interval |
| Measured Parameters |
Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy |
| Averaging Interval |
User selectable: 1, 5, 10, 30 sec, 1, 5, 10, 15, 30 min |
| Averaging Time Min/Max Values |
Voltage, Current: Full cycle RMS updated every half cycle Aux, Power: 200 ms |
| Demand Interval (Energy Meter Mode) |
| Measured Parameters |
Energy (Wh, varh, VAh), PF, maximum demand, cost of energy |
| Interval |
User selectable: 5, 10, 15, 20, 30 min, off |
| Interfaces |
| USB-A |
File transfer via USB flash drive, firmware updates, max. supply current: 120 mA |
| WiFi |
File transfer and remote control via direct connection or WiFi infrastructure |
| Bluetooth |
Read auxiliary measurement data from Fluke Connect® 3000 series modules |
| USB-Mini |
Data download device to PC |
| Voltage Inputs |
| Number of Inputs |
4 (3 phases and neutral) |
| Maximum Input Voltage |
1000 V RMS, CF 1.7 |
| Input Impedance |
10 MΩ |
| Bandwidth |
42.5 Hz to 3.5 kHz |
| Scaling |
1:1 and variable |
| Measurement Category |
1000 V CAT III/600 V CAT IV |
| Current Inputs |
| Number of Inputs |
3, mode selected automatically for attached sensor |
| Input Voltage |
Clamp input: 500/50 mV rms; CF 2.8 |
| Rogowski Coil Input |
150/15 mV rms at 50 Hz 180/18 mV rms at 60 Hz CF 4 All at nominal probe range |
| Bandwidth |
42.5 Hz to 3.5 kHz |
| Scaling |
1:1 and variable |
| Auxiliary Inputs |
| Number of Inputs |
2 |
| Input Range |
0 to ±10 V DC, 1 reading/s |
| Scale Factor |
Format: mx + b (gain and offset) user configurable |
| Displayed Units |
User configurable (7 characters, for example, °C, psi, or m/s) |
| Wireless Connection |
| Number of Inputs |
2 |
| Supported Modules |
Fluke Connect® 3000 series |
| Acquisition |
1 reading/s |
| Environmental Specifications |
| Operating Temperature |
14 to 122°F (-10 to 50°C) |
| Storage Temperature |
−4 to 140°F (-20 to 60°C) With battery: −4 to 122°F (-20 to 50°C) |
| Operating Humidity |
50 to 86°F (10 to 30°C) max. 95% RH 86 to 104°F (30 to 40°C) max. 75% RH 104 to 122°F (40 to 50°C) max. 45% RH |
| Operating Altitude |
6561.7' (2000 m) up to 13,123.4' (4000 m) derate to 1000 V CAT II/600 V CAT III/300 V CAT IV |
| Storage Altitude |
39,370.1' (12,000 m) |
| Enclosure |
IP50 in accordance with EN60529 |
| Vibration |
MIL-T-28800E, Type 3, Class III, Style B |
| Safety |
IEC 61010-1 IEC Mains Input: Overvoltage Category II, Pollution Degree 2 Voltage Terminals: Overvoltage Category IV, Pollution Degree 2 IEC 61010-2-031: CAT IV 600 V/CAT III 1000 V |
| Electromagnetic Compatibility (EMC) |
EN 61326-1: Industrial CISPR 11: Group 1, Class A Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment) USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103 |
| Temperature Coefficient |
0.1 x accuracy specification/°C |
| General Specifications |
| Color LCD Display |
4.3" (109.2 mm) active matrix TFT, 480 x 272 pixels, resistive touch panel |
| Dimensions |
Instrument: 7.8 x 6.6 x 2.2" (19.8 x 16.7 x 5.5 cm) Power supply: 5.1 x 5.1 x 1.8" (13 x 13 x 4.5 cm) |
| Weight |
Instrument: 2.5 lbs (1.1 kg) Power supply: 0.9 lb (400 g) |